38 - Modules Programming Guide
DGP2-PS17 V1.0
Power Supply
A 40VA transformer is required when selecting the 850mA battery charge current. Using a 20VA transformer with a battery charge current
of 850mA may damage the system.
Refer to Appendix 1: Programming PGMs on page 52 for the PGM Table. Only Event Groups 000 to 055 can be used to program the
module’s PGM.
U Default Setting
Section [001] General Options
Option OFF ON
[1]
PGM Tamper Recognition
U PGM Tamper Recognition
N
Tamper report sent to the panel
[2]
Battery Charging Curren
U Battery Charging Current N Charging current at 850mA
[3]
PGM Deactivation After
U Deactivation Event N PGM Timer
[4]
PGM Base Time
U 1 second N 1 minute
[5] to [8]
Future Use
NN/A NN/A
Sections Data Description Default
[002] __/__/__ (001 to 255 X 1 minute, 000 = instant AC Failure Report Delay
n/a
[003]
__/__/__ (000 to 255; refer to option [4] in section [001])
Option [8] must be enabled before the PGM modes can
be tested.
PGM Timer
n/a
Sections PGM Activation Event
[004] __/__/__ Event Group
[005] __/__/__ Feature Group
[006] __/__/__ Start #
[007] __/__/__ End #
Sections PGM Deactivation Event
[008] __/__/__ Event Group
[009 __/__/__ Feature Group
[010] __/__/__ Start #
[011] __/__/__ End #
Section Description
[020] Test PGM: Activates the PGM for 8 seconds to verify if the PGM is functioning properly.