
50 Reference & Installation Manual
17 Appendix 1: DGP2-641BL/RB Installation Instructions
1.0 INSTALLATION
The DGP2-641BL/RB is connected to the control panel's combus
in a star and/or daisy chain configuration. This 4-wire combus
provides power and two-way communication between the control
panel and all modules connected to it. Connect the four terminals
labeled red, black, green and yellow of each keypad to the
corresponding terminals on the control panel (refer to Figure 26 on
page 50). Refer to the DGP-848 Reference & Installation Manual
for the maximum allowable installation distance from the control
panel.
See Figure 29 on page 51 for connection drawings for the REX
device, locking device and door contact to the desired DGP2-
641BL/RB keypad module. A typical installation is shown in Figure
27 on page 50.
The door contact follows the control panel’s EOL definition. When EOL is
enabled and the door contact is not used, place a 1k
Ω
resistor across the
keypad’s Z1 and BLK input terminals. If EOL is not enabled, use a jumper. If
the REX device is not used, place a jumper across the keypad’s Z2 and BLK
input terminals.
Please consider the following when installing the DGP2-
641RB:
• Maintain all DGP2-641RB wiring a minimum of 30cm (12”) away from
other wiring such as AC power, computer data wiring, telephone
wiring, etc.
• Avoid installing within 1.1m (3.5ft.) of computer monitors or CRTs.
The minimum distance will vary depending on the type of monitor or
CRT.
• Avoid installing in proximity to sources of broad spectrum EMI noise
such as motors, pumps, generators, DC to AC converters,
uninterruptible power supplies, AC switching relays, light dimmers,
computer monitors and CRTs.
• Avoid installing in proximity to potential sources of RF signal
transmitters such as cellular phones, two-way radios, etc.
1.1 Mounting the DGP2-641RB on Metal
Although metal may decrease the read range of it’s built-in reader,
the DGP2-641RB can be mounted on metal. However, do not box
in or surround the DGP2-641RB with any kind of metal. If the
keypad module must be installed in any kind of metal enclosure,
ensure that the face of the DGP2-641RB is not covered and that
there is at least 4cm (1.6”) between the keypad module and the
metal on all sides of the DGP2-641RB.
1.2 Connecting Keypad Zones
Each keypad has one traditional hardwired input terminal, allowing
you to connect one detector or door contact directly to the keypad.
For example, a door contact located at the entry point of an
establishment can be wired directly to the input terminal of the
entry point keypad instead of wiring the door contact all the way to
the control panel.
Connect the device to the keypad's input terminal as shown in
Figure 26 on page 50. In order to communicate its status to the
control panel, devices connected to the keypad's input terminal
must be assigned to a zone in the control panel and the zone's
parameters must be defined. For more information on zone
assignment, please refer to the section 4 on page 11. Please note
that even with the ATZ (zone doubling) feature enabled, the keypad
supports only one detection device.
Figure 26 : Connecting the Keypad and Keypad Zone
Figure 27 : Typical Access Control Installation
Figure 28 : Access Control Overview
To Digiplex
series
control panel
Combus
DGP2-641BL/RB
* The keypad zone follows the
control panel’s EOL definition.
The zone speed is set at 600mS
and cannot be programmed.
Door Contact
The keypad’s tamper switch will
communicate its status to the control
panel via the combus.
1 = Request for Exit (REX) device (Paradoor)
2 = Door contact
3 = DGP2-641RB LCD Keypad Module
4 = Locking device
5 = Digiplex series control panel
5
4
3
1
2
Door
Contact
(Z1)
Locking
Device
(PGM)
REX device (Z2)
DGP2-641RB
Combus
To Digiplex series
control panel
Komentarze do niniejszej Instrukcji