26 Reference & Installation Manual
Section [680]
Auto Zone Shutdown: a zone communicates more than the
programmed number of transmissions in a single armed
period (see section 4.4.1 on page 13)
Duress: a Duress enabled access code is keyed in (see
section 13.5.2 on page 39).
8.2.8 Zone Tamper Report Codes
SECTION [681] TO [692]
A report code can be programmed for each of the 48 available
zones. Whenever a tamper or wire fault occurs on a zone, the
control panel can send the appropriate report code to the
monitoring station identifying which zone was tampered. If the
Tamper Recognition Options (see section 7.4 on page 22) are
disabled, the control panel will not report the occurrence of any
tampers or wire faults.
8.2.9 Zone Tamper Restore Codes
SECTIONS [693] TO [704]
A report code can be programmed for each of the 48 available
zones. Whenever a tampered zone is restored, the control panel
can send the appropriate report code to the monitoring station
identifying which zone has been restored.
8.2.10 Special Tamper Report Codes
SECTION [705]
Keypad Lockout: (see section 6.10 on page 20)
8.2.11 System Trouble Codes
SECTIONS [706] TO [711]
Section [706]
AC Failure: no AC input detected on the control panel. The
control panel can delay reporting this event, please refer to
Power Fail Report Delay in section 8.9 on page 28.
Battery Failure: the back up battery is disconnected or the
battery voltage is less than or equal to 10.5V
Auxiliary Supply: the auxiliary power supply’s current is greater
than or equal to 1.1A.
Section [707]
Bell Output: the bell/siren output is disconnected or the current
is greater than or equal to 3A
Clock Loss: the control panel detects a loss in panel time (see
section 12.7 on page 36)
Fire Loop Trouble: a tamper has been detected on a fire zone
(see section 4.2 on page 12)
•N/A
Section [708]
Combus Fault: a module has been removed from the combus.
Module Tamper: a tamper or wire fault is detected on a module
other than a motion detector connected to the combus
ROM Check Error: problem with on-board Read-Only Memory
Module TLM: TLM failure detected on voice dialer connected
to the combus
Section [709]
Module Fail to Communicate: a module has failed to
communicate with the monitoring station
Printer Fault: the Printer Module connected to the combus has
detected an error (see the Printer Module Manual for details).
Module AC Failure: no AC power detected on a module
connected to the combus
Module Battery Failure: the backup battery on a module is
disconnected or the battery voltage is low
Section [710]
Module Auxiliary Failure: the auxiliary output of a module
connected to the combus has exceeded current limits
Wireless Transmitter Low Battery
Wireless Module Supervision Failure: This report code is
global unless using the Contact ID or SIA reporting formats.
Section [711]
Phone Number 1 Fail to Communicate
Phone Number 2 Fail to Communicate
Phone Number 3 Fail to Communicate
Phone Number 4 Fail to Communicate
Please note: there is no Fail to Communicate for Pager
telephone numbers.
8.2.12 System Trouble Restore Codes
SECTION [712] TO [716]
Section [712]
TLM: a TLM failure has restored.
If the Telephone Line Monitoring (see section 9.1 on
page 29) is disabled, the control panel will not transmit
the TLM report code.
AC Failure Restored
Battery Failure Restored
Auxiliary Supply Restored
Section [713]
Bell Output Restored
Time programmed
Fire Loop Trouble Restored
•N/A
Section [714]
Combus Fault Restored
Module Tamper Restored
ROM Check Error Restored
Module TLM Restored
Section [715]
•N/A
Printer Fault Restored
Module AC Failure Restored
Module Battery Failure Restored
Section [716]
Module Auxiliary Failure Restored
Wireless Transmitter Low Battery Restored
Wireless Module Supervision Restored: This report code is
global unless using the Contact ID or SIA Reporting formats.
8.2.13 Special Reporting Codes
SECTION [717] AND [718]
Whenever the system generates one of the following instances, the
control panel can send the appropriate report code to the
monitoring station identifying the type of system occurrence:
Section [717]
Cold Start: the control panel was completely shutdown (total
power loss) and the control panel was re-started
Warm Start: the control panel performs a reset due to any
sudden problem other than power loss
Test Report: report generated automatically (see section 8.8
on page 28)