DGP-848 Control Panel 35
‡ You must program a remote control button with a Utility Key option.
12 System Settings & Commands
12.1 Hardware Reset
Performing a hardware reset will set all programmable sections
from [001] to [718] to default values, including the Installer Code
and System Master Code. Only the Panel ID, PC Password, PC
Telephone Number and Event Buffer will not be reset.
1) Make sure the Installer Code Lock is disabled (see section
12.4 on page 36)
2) Remove the battery and AC power from the control panel.
3) Set the
RESET jumper to on by placing a jumper on the reset
pins of the control panel.
4) Re-connect the AC power and the battery to the control panel.
5) Wait 10 seconds and remove the jumper.
12.2 Software Reset
Performing a software reset will set certain parameters to default
values or program certain sections with a set of pre-defined values.
To do so:
1) Make sure the
RESET jumper on the control panel is on.
2) Enter Panel Programming Mode (see section 3.1 on page 9).
3) Enter the 3-digit [
SECTION] corresponding to the software reset
you wish to perform:
Section [970]
Entering this section will reset all programmable sections from
[001] to [896] (except sections [451] to [498], [555], [556], [560],
[790] to [795], and [800]) to default values. The Zone Labels,
Panel ID, PC Password, PC Telephone Number, Installer Code,
System Master Code, Event Buffer, and Automatic Report Codes
will not be reset.
Section [974]
Entering this section resets the following Access Control sections:
[301] to [332], [340] to [355], [361] to [375], [381] to [392], and
[537].
Section [975]
Entering this section will reset all Zone and Keyswitch
programming sections from [001] to [056], and [101] to [156] to
default values.
Section [976]
Entering this section will reset the following sections to default
values: [200] to [261], [270] to [274], [400] to [409], and [440] to
[442].
Section [977]
Entering this section will reset sections from [500] to [522] to
default values.
Section [978]
Entering this section will reset the following communication
sections to default values: [521] to [536],
[550] to [554], [561] to
[564], and [600] to [718].
Section [979]
Entering this section will reset all user code sections from [801] to
[896] to default values.
12.3 Battery Charge Current
SECTION [503]: OPTION [6]
Option [6] ON = Battery Charge Current: 850mA (minimum 40VA
transformer)
Option [6] OFF = Battery Charge Current: 350mA
A 40VA transformer is required when selecting the
850mA battery charge current. Using a 20VA
transformer with a battery charge current of 850mA
may damage the system.
Table 12: Utility Key Event Generation Table
Event Name
Using Keyswitch
Definition 3
Using Keyswitch
Definition 4
Using Keypad Buttons
Using Remote
Controls
Utility Key 1 Keyswitch 001 opens Keyswitch 001 opens [1] + [2]
Utility Key 1
‡
Utility Key 2 Keyswitch 002 opens Keyswitch 001 closes [4] + [5]
Utility Key 2
‡
Utility Key 3 Keyswitch 003 opens Keyswitch 002 opens [7] + [8]
Utility Key 3
‡
Utility Key 4 Keyswitch 004 opens Keyswitch 002 closes
[CLEAR] + [0] or [*] + [0]
Utility Key 4
‡
Utility Key 5 Keyswitch 005 opens Keyswitch 003 opens [2] + [3]+
Utility Key 5
‡
Utility Key 6 Keyswitch 006 opens Keyswitch 003 closes [5] + [6] ----
Utility Key 7 Keyswitch 007 opens Keyswitch 004 opens [8] + [9] ----
Utility Key 8 Keyswitch 008 opens Keyswitch 004 closes
[0] +
[ENTER] or [0] + [#]
----
Utility Key 9 ---- Keyswitch 005 opens ---- ----
Utility Key 10 ---- Keyswitch 005 closes ---- ----
Utility Key 11 ---- Keyswitch 006 opens ---- ----
Utility Key 12 ---- Keyswitch 006 closes ---- ----
Utility Key 13 ---- Keyswitch 007 opens ---- ----
Utility Key 14 ---- Keyswitch 007 closes ---- ----
Utility Key 15 ---- Keyswitch 008 opens ---- ----
Utility Key 16 ---- Keyswitch 008 closes ---- ----